FSD-TD Series - Installation Methods

Installations tested to EN1366-2 and classified to BS EN 13501-3*
FSD-TD M9 / DW145 M4

Dry Wall with Angle Frame fitted

Single section sizes (mm): 100 x 100 to 1200 x 1200

TESTED FROM BOTH SIDES
Tested to EN1366-2 for 2 hours. Equivalent to BS EN 13501-3 classification: ES120 (E120S)
BS EN 1366-2 test/assessment references: 260152 and 260153/CC261450
Meets the requirement of BS 476-20/22 - refer BS 476-10.6.6.3
* If your proposed installation method has minor variations to that shown above, please confirm acceptance with the local Building Control Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods.